Multi-Function Control ETMFC610
http://www.entecene.co.kr
287
EN
HANCED
TEC
HNOLOGY
8.5.4.2. Forward Power(32FP)
ETMFC610 provides the two of the Forward Power (32FP) elements. If three phase active power is
kept above the pickup level for a certain time, ETMFC610 generates an alarm for this element.
Three phase active power is calculated as below, and it operates only about the forward (positive)
active power.
WYE VT Connection Type
DELTA VT Connection Type
*. Note )
P+
OPERATION
NON-OPERATION
-P
0
Figure 8-50. Forward Power(32FP) Elements Characteristic
The forward power should be enabled to following settings;
GROUP # / MONITORING / POWER / FORWARD POWER /Pickup1
Range
0.00~300.00 MW
Default
0.00
Step
0.01
Set the pickup level of forward power element 1
*. NOTE )
Pickup2 setting is same as Pickup1 setting above.
[FORWARD POWER]
>Pickup1: 0.00
Time Delay1: 5.00
Pickup2: 0.00
Time Delay2: 5.00
0(OFF),0.00~300.00MW