Multi-Function Control ETMFC610
http://www.entecene.co.kr
224
EN
HANCED
TEC
HNOLOGY
6) Other Setup
GROUP #/ PROTECTION/ INRUSH RESTRAINT/ OTHERS / Outage Time
Range
0.01 ~ 10.00 sec
Default
5.00
Step
0.01 sec
Set the outage time. After the outage condition is maintained for more
than the setting time, the restoration of load supply becomes active
and the Inrush current restraint section becomes active.
Outage conditions are as follows;
If "Make Use 'I'" setting is NO, it is considered to be outage when
CB status is open.
If "Make Use 'I'" setting is YES, it is considered to be outage
when current is below 2A.
However, under the above conditions, current should be below
"Outage I".
GROUP #/ PROTECTION/ INRUSH RESTRAINT/ OTHERS / Make Use ‘I’
Range
NO, YES
Default
NO
Step
~
Set whether or not to use current as decision condition for operating
function.
When it sets to NO, the inrush current restraint interval becomes
active when recloser is changed from open to close status.
When it set to YES, when the current increases above 2A, the
inrush current restraint interval is active.
[OTHERS]
>Outage Time: 5.00
>
Make Use ‘I’: NO
[0.01~600.00:0.01 s]
[OTHERS]
>
Outage Time: 5.00
>Make Use ‘I’: NO
[NO/YES]