GLOBAL SETTING / GENERAL / PLC / LOGIC TIMER / TM1-DO
Range
0.01 ~ 600.00 sec
Default
0.05
Step
0.01 sec
Set a Dropout Time of Logic timer 1.
*. NOTE )
TM02~TM08 are same as TM01 above.
7.1.6.2. PULSE TIMER
Place the curser on “PULSE TIMER”, press [ENT] button to move into this menu.
PLC has 8 pulse timer.
When Input A becomes 1 in pulse timer, output B becomes 1, this output comes for Y time.
Please refer to
“Figure 7-16. Pulse Timer Symbol”
In PLC, A shall be input at the user logic IPTM
□
.
In PLC, B is output for PTM
□
.
Figure 7-16. Pulse Timer Symbol
GLOBAL SETTING / GENERAL / PLC / PULSE TIMER / PTM1
Range
0.01 ~ 600.00 sec
Default
0.01
Step
0.01 sec
Set an output time of pulse timer 1.
*. NOTE ) P
TM02~PTM08 are same as PTM01 above.
B
A
Y
0s
PTM□
[LOGIC TIMER]
TM01-Pickup: 0.05
>TM01-Dropout: 0.05
TM02-Pickup: 0.05
TM02-Dropout: 0.05
TM03-Pickup: 0.05
[0.01~600.00:0.01s]
[PULSE TIMER]
>PTM01 Output: 0.01
PTM02 Output: 0.01
PTM03 Output: 0.01
PTM04 Output: 0.01
PTM05 Output: 0.01
[0.01~600.00:0.01s]