Over Voltage
Pickup Level ………………………………….0.10 to 1.40xVT in steps of 0.01xVT
Time Delay……………………………………0.00 to 600.00sec in steps of 0.01sec
Under Frequency
Pickup Level …………………………………..OFF, 45.00 to 65.00Hz in steps of 0.01Hz
Time Delay……………………………………0.00 to 600.00sec in steps of 0.1sec
Over Frequency
Pickup Level …………………………………..OFF, 45.00 to 65.00Hz in steps of 0.01Hz
Time Delay……………………………………0.00 to 600.00sec in steps of 0.01sec
Current Unbalance/THD Detect Limit Current ......... 0 to 630A in steps of 1A
Level Accuracy .......................................................... at VT ± 0.02
㎐
, at CVD ± 0.05
㎐
or ± 5%
Timing Accuracy ....................................................... ± 5% of setting time or ± 20msec
System Power
Function ..................................................................... OFF/ON
+12V Pickup .............................................................. OFF, 0.1 to 10.0 V in steps of 0.1V
Time Delay ................................................................ 0.01 to 10.00 sec in steps of 0.01 sec
-12V Pickup ............................................................... OFF, 0.1 to 10.0 V in steps of 0.1V
Time Delay ................................................................ 0.01 to 10.00 sec in steps of 0.01 sec
Ref. V Pickup ............................................................ OFF, 0.1 to 10.0 V in steps of 0.1V
Time Delay ................................................................ 0.01 to 10.00 sec in steps of 0.01 sec
Level Accuracy .......................................................... ± 5%
Timing Accuracy ....................................................... ± 5% of setting time or ± 20msec