Multi-Function Control ETMFC610
http://www.entecene.co.kr
147
EN
HANCED
TEC
HNOLOGY
GLOBAL SETTING/ COMMUNICATION/ PROTOCOLS / IEC60870-5/ IEC60870-5-104/ SBO Timeout
Range
0(OFF), 0~255
Default
5
Step
1sec
Enter the period after a previously received select will timeout.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOLS / IEC60870-5/ IEC60870-5-104/ MD Termination
Range
NO, YES
Default
YES
Step
~
Select whether to send Activation Termination upon completion of
commands other than set point commands.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOLS / IEC60870-5/ IEC60870-5-104/ CSE Termination
Range
NO, YES
Default
YES
Step
~
Select whether to send Activation Termination upon completion of set
point commands.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOLS / IEC60870-5/ IEC60870-5-104/ Clock Sync’ Evt
Range
NO, YES
Default
YES
Step
~
Select whether to generate spontaneous clock synchronization events
GLOBAL SETTING/ COMMUNICATION/ PROTOCOLS / IEC60870-5/ IEC60870-5-104/ MSP Time-Tag
Range
CP56, CP24
Default
CP56
Step
~
Select whether a time tag format for single-point.
CP56 :
The time tag format is CP56Time2a.
CP24 :
The time tag format is CP24Time2a.
[IEC60870-5-104]
Rx Frame Size: 255
Tx Frame Size: 255
>SBO Timeout: 5
CMD Termination:YES
CSE Termination:YES
[0(OFF),0~255:1]
[IEC60870-5-104]
Rx Frame Size: 255
Tx Frame Size: 255
SBO Timeout: 5
>CMD Termination:YES
CSE Termination:YES
[NO/YES]
[IEC60870-5-104]
Rx Frame Size: 255
Tx Frame Size: 255
SBO Timeout: 5
CMD Termination:YES
>CSE Termination:YES
[NO/YES]
[IEC60870-5-104]
>
CSE Termination:YES
>Clock Sync’ Evt:YES
MSP Time-Tag: CP56
>
MIT Time-Tag: CP56
MME Time-Tag: CP56
[NO/YES]
[IEC60870-5-104]
>
CMD Termination:YES
CSE Termination:YES
Clock Sync’ Evt:YES
>MSP Time-Tag: CP56
MIT Time-Tag: CP56
[CP56/CP24]