Multi-Function Control ETMFC610
http://www.entecene.co.kr
125
EN
HANCED
TEC
HNOLOGY
Table 7-7. Fault Pop-up Screen
FAULT POP-UP SCREEN
①
Fault type is indicated
FAULT : Fault event before the final fault(Permanent fault or
Temporary fault)
P-FI : Permanent fault
T-FI : Temporary fault
51 : Time Overcurrent Trip
50 : Instantaneous Overcurrent Trip
②
Fault Direction
F : Forward fault
R : Reverse fault
- : If it is the final fault event or cannot determine the fault direction ,
fault direction is not indicated.
③
Indicate fault target
A, B, C : each phase fault (Phase fault)
G : Ground fault
Q : Negative Sequence fault
S : Sensitive Earth Fault
④
Fault sequence (shot count) is indicated
⑤
Indicate each phase and negative sequence, S.E.F fault current
⑥
Indicate fault current occurring time
*. Whenever fault is occurred, fault pop-up screen is accumulated, the latest
fault screen is displayed at first.
*. Using [ENT] button, accumulated fault pop-up screen is checked.
*. Using [ESC] button, you can clear the pop-up screen without checking all
fault pop-up screens.
[ALERT] FAULT INFO
TYPE :
①
DIR:
②
TARGET:
③
SEQ:
④
A:
⑤
A B:
⑤
A
C:
⑤
A N:
⑤
A
Q:
⑤
A S:
⑤
A
⑥
[ALERT] FAULT INFO
TYPE :FAULT DIR:F
TARGET:ABCNSQ SEQ:1
A: 00000A B: 00000A
C: 00000A G: 00000A
Q: 00000A S: 00.00A
2017/01/01 00:00:00