GLOBAL SETTING / GENERAL
/
MONITORING / SYSTEM POWER / Time Delay
Range
0.01 ~ 10.00 sec
Default
1.00
Step
0.01 sec
Set delay time of -12V system power alarm.
GLOBAL SETTING / GENERAL
/
MONITORING / SYSTEM POWER / Ref. V Pickup
Range
0(OFF), 0.1 ~ 10.0 V
Default
OFF
Step
0.01 V
Set a pickup value for reference voltage alarm.
If the error of the reference voltage measurement value deviates more
than this setting, an alarm is generated.
GLOBAL SETTING / GENERAL
/
MONITORING / SYSTEM POWER / Time Delay
Range
0.01 ~ 10.00 sec
Default
1.00
Step
0.01 sec
Set delay time of reference voltage alarm.
[SYSTEM POWER]
Function: ON
+12V Pickup: 1.0
Time Delay: 1.00
-12V Pickup: 1.0
>Time Delay: 1.00
Ref. V Pickup: OFF
Time Delay: 1.00
[0.01~10.00:0.01 s]
[SYSTEM POWER]
Function: ON
+12V Pickup: 1.0
Time Delay: 1.00
-12V Pickup: 1.0
Time Delay: 1.00
>Ref. V Pickup: OFF
Time Delay: 1.00
[0(OFF),0.1~10.0V]
[SYSTEM POWER]
Function: ON
+12V Pickup: 1.0
Time Delay: 1.00
-12V Pickup: 1.0
Time Delay: 1.00
Ref. V Pickup: OFF
>Time Delay: 1.00
[0.01~10.00:0.01 s]