Table 8-2. CB time-current operation characteristic setting range
Setting
1
2
3
4
5
6
7
8
9
10
Curve
A(101)
B(117)
C(133)
D(116)
E(132)
IEC-EI
K(162)
L(107)
M(118)
N(104)
Setting
11
12
13
14
15
16
17
18
19
20
Curve
IEC-NI
P(115)
R(105)
T(161)
V(137)
IEC-VI
W(138)
Y(120)
Z(134)
1(102)
Setting
21
22
23
24
25
26
27
28
29
30
Curve
2(135)
3(140)
4(106)
5(114)
6(136)
7(152)
8(113)
8*(111)
9(131)
11(141)
Setting
31
32
33
34
35
36
37
38
39
40
Curve
13(142)
14(119)
15(112)
16(139)
18(151)
N1
N2
N3
N4
US-NI
Setting
41
42
43
44
45
46
47
48
49
50
Curve
US-VI
US-EI
ES-NI
ES-VI
USER-1
USER-2
USER-3
USER-4
DEF-1S
DEF-10S
Setting
51
52
53
54
55
56
57
58
59
60
Curve
IEEE-NI
IEEE-VI
IEEE-EI
US-STI US-STVI
IEC-LTI
IEC-STI
ES-LTVI
ES-EI
RI
Setting
61
62
Curve
HR
FR
GROUP # / PROTECTION / TIME OC-PHA / (+)TIME OC-PHA / Time Dial
Range
0.01 ~ 15.00
Default
1.00
Step
0.01
Set time dial, multiplying this value to selected T-C curve. Multiplying
this value changes the slope of the curve. Time dial is conducted after
time add application.
GROUP # / PROTECTION / TIME OC-PHA / (+)TIME OC-PHA / Time Add
Range
0.00 ~ 600.00 sec
Default
0.00
Step
0.01 sec
Set Time adder to add set value on selected T-C curve.
[(+)TIME OC-PHA]
Function: ENABLE
Pickup: 500
Curve: [US-VI]
>Time Dial: 1.00
Time Add.: 0.00
[0.05~15.00:0.01]
[(+)TIME OC-PHA]
Function: ENABLE
Pickup: 500
Curve: [US-VI]
Time Dial: 1.00
>Time Add.: 0.00
[0.00~600.00:0.01s]