Multi-Function Control ETMFC610
http://www.entecene.co.kr
286
EN
HANCED
TEC
HNOLOGY
8.5.4. Power (32)
Place the curser on “POWER” in MONITORING menu, press [ENT] button to move into this
menu. In this menu, forward power elements and directional power elements will be described.
And the power setting menus are composed with 3 sub-menus as follows:
8.5.4.1. Common Setting for Power elements
This setting applies to all power elements of forward power and directional power elements;
GROUP # / MONITORING / POWER / Function
Range
DISABLE, ENABLE
Default
DISABLE
Step
~
Set the function of power elements as enable or disable.
If function = DISABLE,
the feature is not operational.
If function = ENABLE,
the feature is operational. When the feature
asserts an alarm condition, the device gives the alarm.
GROUP # / MONITORING / POWER / BLK After CL
Range
0.02~600.00 sec
Default
5.00
Step
0.01sec
Set the Block Time After Close for power elements.
To prevent malfunction of power elements by inrush current incurred at
the restoration of load supply, set the time that each power element
’
s
operation is suppressed after the restoration of load supply. After close
operation, all function for power elements are blocked during this set
time.
[FUNCTION]
>Function: DISABLE
BLK After RS: 5.00
[
DISABLE/ENABLE]
[FUNCTION]
>Function: DISABLE
BLK After CL: 5.00
[
0.02~600.00:0.01s]
[POWER]
>1.FUNCTION
2.FORWARD POWER
3.DIRECTIONAL POWER