Multi-Function Control ETMFC610
http://www.entecene.co.kr
26
EN
HANCED
TEC
HNOLOGY
SYSTEM EVENT RECORDER
Trigger Source
Protection Elements
52A Contact
Sequence status
Front panel control
AC supply
External control
Fail operation
External input status
System alarm, etc.
Trigger Time : every 5 msec
Trigger type : Pick up and Dropout
Storage Capacity : Last 5,000 Events
SET CHANGE EVENT RECORDER
Trigger Source
Global Setting Change
Group Setting Change – Group 1/2/3/4/5/6
Storage Capacity : Total 2,000 Events
LOAD & ENERGY
1) Average Load/ Minute
Trigger Source
Demand Current – A, B, C, N
Demand Voltage – A, B, C, R, S, T
Demand Real Power – A, B, C, 3
ф
, Positive A, Positive B, Positive C, Positive 3
ф
,
Negative A, Negative B, Negative C, Negative 3
ф
Demand Reactive Power – A, B, C, 3
ф
, Positive A, Positive B, Positive C, Positive 3
ф
,
Negative A, Negative B, Negative C, Negative 3
ф
Demand Power Factor – A, B, C, 3
ф
Demand Energy - Positive Watthour(3
ф
), Positive Varhour(3
ф
), Negative Watthour(3
ф
),
Negative Varhour(3
ф
)
Trigger Time : every 5, 10, 15, 20, 30 or 60 minutes
Storage Capacity : Total 8,640 Events