Multi-Function Control ETMFC610
http://www.entecene.co.kr
207
EN
HANCED
TEC
HNOLOGY
GROUP # / PROTECTION / TIME OC-NEQ / (+)TIME OC-NEQ / Low Set DT
Range
0(OFF), 0.01 ~ 600.00 sec
Default
OFF
Step
0.01 sec
Low set definite time is used to restrict a trip time to be a definite time
adjacent to a pickup current by T-C curve. When the trip time is greater
than the low set definite time, low set definite time is applied for
operation.
2) (-)TIME OC-NEQ Setup
‘(-)TIME OC-NEQ’ settings are very similar ‘(+)TIME OC-NEQ’ time overcurrent setting.
[(+)TIME OC-NEQ]
Curve: [US-VI]
Time Add.: 0.00
M.R.T: 0.00
Reset Method: INST
>Low Set DT: OFF
0(OFF),0.01~600.00s