Multi-Function Control ETMFC610
http://www.entecene.co.kr
144
EN
HANCED
TEC
HNOLOGY
GLOBAL SETTING/ COMMUNICATION/ PROTOCOLS / IEC60870-5/ IEC60870-5-101/ MIT Time-Tag
Range
CP56, CP24
Default
CP56
Step
~
Select whether a time tag format for integrated totals.
CP56 :
The time tag format is CP56Time2a.
CP24 :
The time tag format is CP24Time2a.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOLS / IEC60870-5/ IEC60870-5-101/ MME Time-Tag
Range
CP56, CP24
Default
CP56
Step
~
Select whether a time tag format for measured value and normalized
value for general event except for fault current event.
CP56 :
The time tag format is CP56Time2a.
CP24 :
The time tag format is CP24Time2a.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOLS / IEC60870-5/ IEC60870-5-101/ Flt Time-Tag
Range
CP56, CP24
Default
CP56
Step
~
Select whether a time tag format for integrated totals.
CP56 :
The time tag format is CP56Time2a.
CP24 :
The time tag format is CP24Time2a.
2) IEC60870-5-104
Move to
“MAIN MENU/ GLOBAL SETTING/ COMMUNICATION/ PROTOCOL/ IEC60870-
5/ IEC60870-5-104”
to select setting for IEC60870-5-104.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOLS / IEC60870-5/ IEC60870-5-104/ Function
Range
DISABLE, ENABLE
Default
DISABLE
Step
~
Set whether IEC60870-5-104 protocol is used for communication.
[IEC60870-5-101]
CMD Termination:YES
CSE Termination:YES
Clock Sync’ Evt:YES
MSP Time-Tag: CP56
>MIT Time-Tag: CP56
[CP56/CP24]
[IEC60870-5-101]
>MME Time-Tag: CP56
>
Flt Time-Tag: CP56
[CP56/CP24]
[IEC60870-5-101]
>
MME Time-Tag: CP56
>Flt Time-Tag: CP56
[CP56/CP24]
[IEC870-5-104]
>Function: DISABLE
ASDU Address: 0
Cyclic Period: 60
Timeout(t0): 120
[DISABLE/ENABLE]