Multi-Function Control ETMFC610
http://www.entecene.co.kr
25
EN
HANCED
TEC
HNOLOGY
2.10. Recorder
OPERATION EVENT RECORDER
Trigger Source
Switch(or CB) Closed(Manual/Remote/Auto/External/Panel Control CLOSE)
Switch(or CB) Opened(Manual/Remote/Auto/External/Panel Control OPEN)
Storage Capacity : Total 5,000 Events
FAULT EVENT RECORDER
Trigger Source
Fault Indication(applied when Fault Indication type)
Fault Trip(applied when Protection type)
Data Channels
Analog 14 Channels (Ia, Ib, Ic, Ig, Isef, I1, I2, 3I0, Va, Vb, Vc, Vr, Vs, Vt)
Storage capacity : 1,500 events
FAULT WAVEFORM CAPTURE
Trigger Source
Fault Pickup
Fault Timeout Elements
Data Channels
Current 5 Channels(Ia, Ib, Ic, Ig, Isef)
Voltage 6 Channels(Va, Vb, Vc, Vr, Vs, Vt)
Digital Input Port Status 8 or 20 Channels (IN101~112, IN201~208)
Digial Output Relay 8 or 16 Channels (OUT101~108 ,OUT201~207, OUT214)
Digital Logic Channels
Sample Rate : 16/32/64 per cycle
Trigger Position : 1 to 60 cycles(64 sampling base and depending on the sample rate, it changes)
Storage capacity : 32 events with max 240cycles(Cycle is dependent on Sample Rate)
Содержание ETMFC610
Страница 2: ......
Страница 10: ......
Страница 110: ...Multi Function Control ETMFC610 http www entecene co kr 100 ENHANCED TECHNOLOGY Figure 7 6 Tie Algorithm ...