GROUP # / MONITORING / FREQUENCY / OVER FREQUENCY1 / Reset Time
Range
0.00 ~ 600.00 sec
Default
2.00
Step
0.01 sec
Sets the time to reset the overfrequency element.
GROUP # / MONITORING / FREQUENCY / OVER FREQUENCY1 / Min. V
Range
0.00~1.40 xVT
Default
0.10
Step
0.01 xVT
Enter the minimum voltage required to allow the overfrequency
element and overfrequency to operate.
GROUP # / MONITORING / FREQUENCY / OVER FREQUENCY1 / Min. I
Range
0(OFF), 1 ~ 630A
Default
60
Step
1A
Enter the minimum value of current required for any phase to allow the
overfrequency element to operate.
2) OVER FREQUENCY 2 Setup
The overfrequency 2 settings process a very similar method to the overfrequency 1.
[OVER FREQUENCY1]
Function: DISABLE
Pickup: 62.50
Time Delay: 2.00
>Reset Time: 2.00
Min. Volt: 0.10
[0.00~600.00:0.01s]
[OVER FREQUENCY1]
Pickup: 62.50
Time Delay: 2.00
Reset Time: 2.00
>Min. Volt: 0.10
Min. I: 60
[0.00~1.40:0.01 xVT]
[OVER FREQUENCY1]
Pickup: 62.50
Time Delay: 2.00
Reset Time: 2.00
Min. Volt: 0.10
>Min. I: 60
[0(OFF),1~630:1A]