Multi-Function Control ETMFC610
http://www.entecene.co.kr
96
EN
HANCED
TEC
HNOLOGY
GLOBAL SETTING / GENERAL
/
LOOP CONTROL / SEC Operate Cnt
Range
1 ~ 5 shot
Default
1
Step
~
Set the operation count of the Auto Sectionalizer.
After sensing a fault current, Live line becomes Dead line
Voltage(DV), 1 is counted and sense another fault, the count
accumulate as 2.
When the count reaches a set value,
“SEC Oper’ TD”
Timer is
operated.
When the count is over the set value,
“SEC Oper’ TD”
Timer is
reset and not operated.
Counter is reset by
“SEC Oper’ TD”
Timer or by manual closing.
GLOBAL SETTING / GENERAL
/
LOOP CONTROL / SEC Oper’ TD
Range
0.00 ~ 600.00 sec
Default
0.00
Step
0.01
Set the open operation time delay of the Auto Sectionalizer.
The timer is operated by
“SEC Operate Cnt”
, and after a set time,
Auto Sectionalizer is opened.
The timer is reset if Live Line becomes LV during counting Time,
and it is also reset when the counter is over
“SEC Operate Cnt”
set
value.
GLOBAL SETTING / GENERAL
/
LOOP CONTROL / SEC Reset TD
Range
1.00 ~ 600.00 sec
Default
10.00
Step
0.01
Set the reset time delay of the Auto Sectionalizer.
It is the Timer to reset a count value in
“SEC Operate Cnt”
.
When Auto Sectionalizer is closed, if Source side or Load side
becomes Live Voltage (LV), Timer reset “Sec Oper’ Cnt”.
[LOOP CONTROL]
>
Type Select: OFF
>SEC Operate Cnt: 1
SEC Oper’ TD: 0.00
SEC Reset TD: 10.00
TIE Operate Cnt: 2
[1~5:1]
[AUTO SECTION]
>
Type Select: OFF
SEC Operate Cnt: 1
>SEC Oper’ TD: 0.00
SEC Reset TD: 10.00
TIE VRS: VS
[0.00~600.00:0.01]
[AUTO SECTION]
>
Type Select: OFF
SEC Operate Cnt: 1
SEC Oper’ TD: 0.00
>SEC Reset TD: 10.00
TIE VRS: VS
[1.00~600.00:0.01 s]