Multi-Function Control ETMFC610
http://www.entecene.co.kr
275
EN
HANCED
TEC
HNOLOGY
1) UNDER VOLT1 Setup
The undervoltage 1 should be enabled to following settings.
GROUP # / MONITORING / VOLTAGE / UNDER VOLT1 / Function
Range
DISABLE, ENABLE
Default
DISABLE
Step
~
Set the function of under voltage 1 element as enable or disable.
If function = DISABLE,
the feature is not operational.
If function = ENABLE,
the feature is operational. When the feature
asserts an alarm condition, the device gives the alarm.
GROUP # / MONITORING / VOLTAGE / UNDER VOLT1 / Pickup
Range
0.10~1.40 xVT
Default
0.80
Step
0.01 xVT
Enter the pickup value for under voltage 1 element.
This setting is the ratio of the rated voltage. If the set value is 0.80xVT
and the phase rated voltage is 13.2kV, the phase voltage should be less
than 10.56kV (= 13.2kV * 0.80) to operate this element.
GROUP # / MONITORING / VOLTAGE / UNDER VOLT1 / Time Delay
Range
0.00 ~ 600.00 sec
Default
5.00
Step
0.01 sec
Set the time delay to operate this element. If the voltage is maintained
during this time delay below the pickup level, this element will operate.
GROUP # / MONITORING / VOLTAGE / UNDER VOLT1 / Min. V
Range
0.10~1.40 xVT
Default
0.10
Step
0.01 xVT
Set the minimum voltage to operate this element. This setting is the
ratio of the rated voltage.
[UNDER VOLT1]
>Function: DISABLE
Pickup: 0.80
Time Delay: 5.00
Min. V: 0.10
Voltage Type: 1P
[DISABLE/ENABLE]
[UNDER VOLT1]
Function: DISABLE
>Pickup: 0.80
Time Delay: 5.00
Min. V: 0.10
Voltage Type: 1P
[0.10~1.40:0.01 xVT]
[UNDER VOLT1]
Function: DISABLE
Pickup: 0.80
>Time Delay: 5.00
Min. V: 0.10
Voltage Type: 1P
[0.00~600.00:0.01s]
[UNDER VOLT1]
Function: DISABLE
Pickup: 0.80
Time Delay: 5.00
>Min. V: 0.10
Voltage Type: 1P
[0.10~1.40:0.01 xVT]