Multi-Function Control ETMFC610
http://www.entecene.co.kr
75
EN
HANCED
TEC
HNOLOGY
GLOBAL SETTING / GENERAL
/
EVENT RECORDER / COMTRADE Record
Range
OFF, ON
Default
OFF
Step
~
In case of occurring a fault, set COMTRADE (Common Format for
Transient Data Exchange) format file in EVRC2A-NT.
The COMTRADE file recorded in EVRC2A-NT can be downloaded by
the file transfer protocol function. For details, refer to
“16.2.
COMTRADE”
.
GLOBAL SETTING / GENERAL
/
EVENT RECORDER / COMTRADE Rev.
Range
1999, 2013
Default
1999
Step
~
Select version of COMTRADE file.
GLOBAL SETTING / GENERAL
/
EVENT RECORDER / COMTRADE P/S
Range
P(1ST), S(2ND)
Default
P(1ST)
Step
~
Select whether the analog data value recorded in the COMTRADE file
is primary or secondary data.
GLOBAL SETTING / GENERAL
/
EVENT RECORDER / COMTRADE Rate
Range
1 ~ 10
Default
1
Step
1
Sets the rate of the analog data value recorded to the COMTRADE file.
Record the value divided by the analog data into the COMTRADE file.
[EVENT RECORDER]
>
L&E Record: OFF
>
L&E Interval: 15
>COMTRADE Record:OFF
COMTRADE Rev.: 1999
>
COMTRADE P/S:P(1ST)
[OFF/ON]
[EVENT RECORDER]
>
L&E Record: OFF
>
L&E Interval: 15
>
COMTRADE Record:OFF
>COMTRADE Rev.: 1999
>
COMTRADE P/S:P(1ST)
[1999/2013]
[EVENT RECORDER]
>
L&E Interval: 15
>
COMTRADE Record:OFF
>
COMTRADE Rev.: 1999
>COMTRADE P/S:P(1ST)
>
COMTRADE Rate: 1
[P(1ST)/S(2ND)]
[EVENT RECORDER]
>
L&E Interval: 15
>
COMTRADE Record:OFF
>
COMTRADE Rev.: 1999
>
COMTRADE P/S:P(1ST)
>COMTRADE Rate: 1
[1~10:1]
Содержание ETMFC610
Страница 2: ......
Страница 10: ......
Страница 110: ...Multi Function Control ETMFC610 http www entecene co kr 100 ENHANCED TECHNOLOGY Figure 7 6 Tie Algorithm ...