91
Installation Variations
Setpoint Wiring Variations
Digital Setpoint Source — RS485 Network, RS232
to RS485 Converter
(TESCOM™ Model #85061)
The USB protocol isn’t networkable, so applications requiring
multiple controllers must use RS485. RS485, wired through a
converter as shown in Figure 29, allows for up to 32 ER5000s to be
daisychained in a network.
WARNING
The controller must be disconnected from the power supply before
any additional wiring or change to jumper configuration is
performed. Do not reconnect the power supply until all additional
wiring connections have been made and are properly installed.
(continued next page)
GRAY
GRAY
GRAY
- RS485
+24 V DC
+ RS485
GROUND
GREEN
GREEN
GREEN
VIOLET
VIOLET
VIOLET
BLUE
BLUE
BLUE
Figure 29: Multiple Controllers in an RS485 Network (RS232 to RS485 Converter)
Содержание Tescom ER5000 Series
Страница 2: ...2 Safety Installation Operations Precautions ...
Страница 9: ...9 Table of Contents ...
Страница 14: ...14 Features and Specifications ...
Страница 25: ...25 What s New ...
Страница 29: ...29 How It Works ...
Страница 44: ...44 Glossary of Terms ...
Страница 57: ...57 Getting Started ...
Страница 76: ...76 Installation Variations ...
Страница 111: ...111 The ERTune Program ...
Страница 116: ...116 The ERTune Program Basic Features ...
Страница 187: ...187 The ERTune Program Power User ...
Страница 196: ...196 ER5000 Software Development Support ...
Страница 202: ...202 Troubleshooting ...
Страница 221: ...221 Internal Variables ...
Страница 236: ...236 Certifications and Warranty ...
Страница 241: ...241 Appendix A Setting up the ERTune Program on Windows 8 PCs ...