Troubleshooting
4. If variable #77 isn’t reading properly, check wiring. Refer to the
Profile with External Control/Digital Inputs
wiring configuration.
5. Use a Read/Write field in
The Read/Write Panel
to monitor
and, if necessary change,
85:AD_EXTRA1–TOGGLE
. Variable #85
(ID_AD_EXTRA1_TOGGLE ) is used to adjust the level at which
the ER5000 interprets variable #77 as a Logical 0 or a Logical 1.
To change the level at which the input switches between
Logical 0 and Logical 1, use the
Write
feature.
•
85:AD_EXTRA1–TOGGLE
is a 12-bit variable with a range
of 400–3700, where a value of 400 counts is 0% and
3700 counts is 100%. To convert between counts and
percent, use the following formulas:
value_percent = (value_counts - 400) * 100 / 3,300
value_counts = ( value_percent * 3,300 /100) + 400
•
The default toggle level is 50% or 2050 counts.
•
The ER5000 Software includes a Unit Converter
program which can assist you in conversion calculations.
It is accessed by clicking the
Unit Converter
button in
the
Resources
section. Refer to the
ER5000 Software
Development Support
section for more information on
accessing the
Resources
section.
Input – If the Profile Does Not Start at a Digital Input from
Digital Input 2
1. Check
Jumper J15
. It must be
OFF
to use Input 2 as a digital
input. Refer to
Checking the Configuration of the Jumpers
earlier in this section.
2. Check variable #78 ( ID_COMPENSATED_EXTRA_AD2). The
value should read higher when the input is activated (Logical
1) than when not activated (Logical 0).
3. Use one of the extra variables on the plot screen to monitor
Extra Analog Input 1 (78)
. Follow the steps in
To add a variable to
the Plot Screen display
.
OR
Use a Read/Write field in
The Read/Write Panel
to monitor
78:COMP_EXTRA–AD1
.
4. If variable #78 isn’t reading properly, check wiring. Refer to the
Profile with External Control/Digital Inputs
wiring configuration.
5. Use a Read/Write field in
The Read/Write Panel
to monitor
and, if necessary change,
86:AD_EXTRA2–TOGGLE
. Variable #86
(ID_AD_EXTRA2_TOGGLE ) is used to adjust the level at which
the ER5000 interprets variable #78 as a Logical 0 or a Logical 1.
To change the level at which the input switches between
Logical 0 and Logical 1, use the
Write
feature.
(continued next page)
Содержание Tescom ER5000 Series
Страница 2: ...2 Safety Installation Operations Precautions ...
Страница 9: ...9 Table of Contents ...
Страница 14: ...14 Features and Specifications ...
Страница 25: ...25 What s New ...
Страница 29: ...29 How It Works ...
Страница 44: ...44 Glossary of Terms ...
Страница 57: ...57 Getting Started ...
Страница 76: ...76 Installation Variations ...
Страница 111: ...111 The ERTune Program ...
Страница 116: ...116 The ERTune Program Basic Features ...
Страница 187: ...187 The ERTune Program Power User ...
Страница 196: ...196 ER5000 Software Development Support ...
Страница 202: ...202 Troubleshooting ...
Страница 221: ...221 Internal Variables ...
Страница 236: ...236 Certifications and Warranty ...
Страница 241: ...241 Appendix A Setting up the ERTune Program on Windows 8 PCs ...