ER5000
—
167
The ERTune™ Program: Basic Features
Additional Commands Available for “F” Model ER5000s
Soak
Pauses the Profile while the ER5000 responds to a step setpoint
change, then dwells at that setpoint for a specified amount of
time. The
Error Band (psig)
field sets the range (+/-) around the
setpoint. When feedback falls within this range, the ER5000
maintains the new setpoint for the amount of time, in seconds,
entered in the
Time to Soak (sec)
entry field.
NOTE
NOTE
CAUTION
CAUTION
WARNING
WARNING
The Dwell command counts off the specified time regardless of
ER5000 response. The Soak command accounts for rise and settling time
before counting off the specified time.
If
Allows the Profile to respond to the current state of the system.
Checks whether a parameter of the current system status matches
the condition specified in the
Condition, Operator and Value
fields.
•
If the condition is TRUE, the next command in the Profile
is executed.
•
If the condition is FALSE, the next command is skipped.
NOTE
NOTE
CAUTION
CAUTION
WARNING
WARNING
To execute a multi-line command sequence based on the same
condition, use the If command together with the
Goto
command, which
is described on the next page.
Содержание Tescom ER5000 Series
Страница 2: ...2 Safety Installation Operations Precautions ...
Страница 9: ...9 Table of Contents ...
Страница 14: ...14 Features and Specifications ...
Страница 25: ...25 What s New ...
Страница 29: ...29 How It Works ...
Страница 44: ...44 Glossary of Terms ...
Страница 57: ...57 Getting Started ...
Страница 76: ...76 Installation Variations ...
Страница 111: ...111 The ERTune Program ...
Страница 116: ...116 The ERTune Program Basic Features ...
Страница 187: ...187 The ERTune Program Power User ...
Страница 196: ...196 ER5000 Software Development Support ...
Страница 202: ...202 Troubleshooting ...
Страница 221: ...221 Internal Variables ...
Страница 236: ...236 Certifications and Warranty ...
Страница 241: ...241 Appendix A Setting up the ERTune Program on Windows 8 PCs ...