Troubleshooting
•
86:AD_EXTRA2–TOGGLE
is a 12-bit variable with a range
of 400–3700, where a value of 400 counts is 0% and
3700 counts is 100%. To convert between counts and
percent, use the following formulas:
value_percent = (value_counts - 400) * 100 / 3,300
value_counts = ( value_percent * 3,300 /100) + 400
•
The default toggle level is 50% or 2050 counts.
•
The ER5000 Software includes a Unit Converter
program which can assist you in conversion calculations.
It is accessed by clicking the
Unit Converter
button in
the
Resources
section. Refer to the
ER5000 Software
Development Support
section for more information on
accessing the
Resources
section.