ER5000
—
216
Troubleshooting
RS485 Communication
TESCOM™ Model # 82948 USB to RS485 Converter
Locate the four DIP switches on the back of the converter. The
switches should be configured as follows:
•
RS485
•
Echo OFF
•
2 Wire
•
2 Wire
Third Party RS232 to RS485 Converters
RS232 to RS485 converters range in modes of operation. If your
application requires an RS232 to RS485 converter, it must be
configured as follows:
•
Echo off.
•
Transmitted data, SD, is used for flow control.
•
No handshake control (RTS/CTS, DSR/DTR)
Additionally, for 4-wire RS422 converters (half duplex):
•
Connect: +TD to +RD
•
Connect: –TD to –RD
Acceptable Resistance Values
The resistance values must be measured with all external wiring
disconnected, including the power. Ensure converter screw
terminals are tight.
Resistance levels outside the acceptable ranges may indicate
damaged RS485 components on the ER5000. Contact your
TESCOM representative.
ER5000 RS485 Interface
•
+RS485 to GND = 10KΩ to 50KΩ
•
–RS485 to GND = 10KΩ to 50KΩ
Converter RS485 Interface
•
+RS485 to GND = 3KΩ to 5KΩ
•
–RS485 to GND = 900Ω to 1.2KΩ
Содержание Tescom ER5000 Series
Страница 2: ...2 Safety Installation Operations Precautions ...
Страница 9: ...9 Table of Contents ...
Страница 14: ...14 Features and Specifications ...
Страница 25: ...25 What s New ...
Страница 29: ...29 How It Works ...
Страница 44: ...44 Glossary of Terms ...
Страница 57: ...57 Getting Started ...
Страница 76: ...76 Installation Variations ...
Страница 111: ...111 The ERTune Program ...
Страница 116: ...116 The ERTune Program Basic Features ...
Страница 187: ...187 The ERTune Program Power User ...
Страница 196: ...196 ER5000 Software Development Support ...
Страница 202: ...202 Troubleshooting ...
Страница 221: ...221 Internal Variables ...
Страница 236: ...236 Certifications and Warranty ...
Страница 241: ...241 Appendix A Setting up the ERTune Program on Windows 8 PCs ...