Safety
Information
Product
Information
Mechanical
Installation
Electrical
Installation
Getting
Started
Basic
parameters
Running
the motor
Optimization
SMARTCARD
operation
PC tools
Advanced
parameters
Technical
Data
Diagnostics
UL Listing
Information
Affinity User Guide
109
Issue Number: 5 www.controltechniques.com
6.2.8 Current demand filter
RFC
A first order filter, with a time constant defined by Pr
0.17
, is provided on
the current demand to reduce acoustic noise and vibration produced as
a result of position feedback quantization noise. The filter introduces a
lag in the speed loop, and so the speed loop gains may need to be
reduced to maintain stability as the filter time constant is increased.
6.2.9 Spin start boost
If Pr
0.33
is set to a non zero value, then Pr
0.18
defines a scaling
function used by the algorithm that detects the speed of the motor. It is
likely that for smaller motors the default value of 1.0 is suitable, but for
larger motors this parameter may need to be increased. If the value of
Pr
0.18
is too large then the motor may accelerate from standstill when
the drive is enabled. If the value of Pr
0.18
is too small then the drive will
detect the motor speed as zero even if the motor is spinning.
6.2.10 Analog input
In modes 2 & 3 a current loop loss trip is generated if the current falls
below 3mA.
In modes 2 & 4 the analog input level goes to 0.0% if the input current
falls below 4mA.
Pr
0.20
sets the destination of analog input 2.
In modes 2 & 3 a current loop loss trip is generated if the current falls
below 3mA.
In modes 2 & 4 the analog input level goes to 0.0% if the input current
falls below 4mA.
6.2.11 Real time clock
The value of Pr
0.24
determines the data displayed in Pr
0.22
and
Pr
0.23
as shown in the table below:
Pr
0.22
shows the date in the format ddmmyy (Pr
0.25
= 0 or 1) or
mmddyy (Pr
0.25
= 2 or 3). Pr
0.23
shows the time in hh.mm format.
If Pr
0.24
is set to 0 or 4 then the date and time start from zero, the days
roll over after 30, and the months roll over after 11.
0.17 {4.12}
Current demand filter time constant
RW
Uni
US
RFC
Ú
0.0 to 25.0 ms
Ö
0.0
0.18 {5.40}
Spin start boost
RW
Uni
US
Ú
0.0 to 10.0
Ö
1.0
0.19 {7.11}
Analog input 2 mode
RW
Txt
US
Ú
0 to 6
Ö
4-20 (4)
Pr
value
Pr
string
Mode
Comments
0
0-20
0 - 20mA
1
20-0
20 - 0mA
2
4-20.tr
4 - 20mA with trip on loss
Trip if I < 3mA
3
20-4.tr
20 - 4mA with trip on loss
Trip if I < 3mA
4
4-20
4 - 20mA with no trip on loss
0.0% if I
≤
4mA
5
20-4
20 – 4mA with no trip on loss
100% if I
≤
4mA
6
VOLt
Voltage mode
0.20 {7.14}
Analog input 2 destination
RW
Uni
DE
PT
US
Ú
Pr
0.00
to Pr
21.51
Ö
Pr
1.37
0.21 {7.15}
Analog input 3 mode
RW
Txt
PT
US
Ú
0 to 9
Ö
VoLt (6)
Pr
value
Pr
string
Mode
Comments
0
0-20
0 - 20mA
1
20-0
20 - 0mA
2
4-20.tr
4 - 20mA with trip on loss
Trip if I < 3mA
3
20-4.tr
20 - 4mA with trip on loss
Trip if I < 3mA
4
4-20
4 - 20mA with no trip on loss
0.0% if I
≤
4mA
5
20-4
20 - 4mA with no trip on loss
100% if I
≤
4mA
6
VOLt
Voltage mode
7
th.SC
Thermistor mode with short-
circuit detection
Th trip if R > 3K3
Th reset if R < 1K8
ThS trip if R < 50R
8
th
Thermistor mode with no
short-circuit detection
Th trip if R > 3K3
Th reset if R < 1K8
9
th.diSp
Thermistor mode with
display only and no trip
0.22 {6.16}
Date
RW
Uni
NC
PT
US
Ú
0 to 311299
Ö
0.23 {6.17}
Time
RW
Uni
NC
PT
US
Ú
0.00 to 23.59
Ö
0.24 {6.19}
Date / time selector
RW
Uni
US
Ú
0 to 5
Ö
3
0.25 {6.20}
Date format
RW
Txt
US
Ú
Std (0), Std.ds (1), US (2),
US.ds (3)
Ö
EUR> Std (0)
USA> US (2)
Pr 0.24
Data displayed in Pr 0.22 and Pr 0.23
0
Drive powered-up time: Date and time starts from zero at
each power-up
1
Date and time from real time clock in slot 1 Solutions Module.
If the module does not support this feature or no module is
installed in slot 1, then the date and time will be zero
2
Date and time from real time clock in slot 2 Solutions Module.
If the module does not support this feature or no module is
installed in slot 2, then the date and time will be zero
3
Date and time from internal real time clock
4
Drive running time: Time that the drive inverter has been
active since it was manufactured
5
Set date and time: Date and time can be adjusted and written
to all Solutions Modules installed which support real time
clock
Содержание Affinity
Страница 274: ...0474 0000 05 ...