103
Issue Number: 5 www.controltechniques.com
Key:
0.39
Motor pre-heat current magnitude
{
6.52
}
0 to 100 %
0
0.40
Autotune
{
5.12
}
0 to 2
0 to 4
0
0.41
Maximum switching frequency
{
5.18
}
3 (0), 4 (1), 6 (2), 8 (3), 12 (4), 16 (5) kHz
3 (0)
0.42
No. of motor poles
{
5.11
}
0 to 60 (Auto to 120 pole)
0 (Auto)
0.43
Motor rated power factor
{
5.10
}
0.000 to 1.000
0.850
0.44
Motor rated voltage
{
5.09
}
0 to AC_VOLTAGE_SET_MAX V
200V drive: 230
400V drive: EUR> 400, USA> 460
575V drive: 575
690V drive: 690
0.45
Motor rated full load speed (rpm)
{
5.08
}
0 to 180,000 rpm
0.00 to
40,000.00 rpm
EUR> 1,500
USA> 1,800
EUR> 1,450.00
USA> 1,770.00
0.46
Motor rated current
{
5.07
}
0 to RATED_CURRENT_MAX A
RATED_CURRENT_MAX
0.47
Rated frequency
{
5.06
}
0 to 3,000.0 Hz
0 to 1,250.0 Hz
EUR> 50.0
USA> 60.0
0.48
Operating mode selector
{
11.31
}
OPEn LP (1), RFC (2),
OPEn LP (1)
RFC (2)
0.49
Security status
{
11.44
}
L1 (0), L2 (1), Loc (2)
0.50
Software version
{
11.29
}
1.00 to 99.99
0.51
Positive logic select
{
8.29
}
OFF (0) or On (1)
On (1)
0.52
Timer 1 start date
{
9.35
}
0 to 311299
0
0.53
Timer 1 start time
{
9.36
}
0.00 to 23.59
0.00
0.54
Timer 1 stop date
{
9.37
}
0 to 311299
0
0.55
Timer 1 stop time
{
9.38
}
0.00 to 23.59
0.00
0.56
Timer 1 repeat function
{
9.39
}
0 to 6
0
0.57
Timer 1 enable
{
9.40
}
OFF (0) or On (1)
OFF (0)
0.58
Timer 1 destination
{
9.43
}
Pr
0.00
to Pr
50.99
Pr
0.00
* Modes 1 and 2 are not user saved, Modes 0, 3 and 4 are user saved