Issue Number: 5 www.controltechniques.com
For size 1 to 6 standard drives, size 1 to 3 E12/54 drives and size 1 to 3 E12/E66 drives, the continuous current ratings given are for maximum 40
°
C
(104
°
F),1000m altitude and 3.0kHz switching. For size 4 to 6 E12/54 drives, the continuous current ratings given are for maximum 35
°
C
(95
°
F),1000m altitude and 3.0kHz switching. For further information refer to section 12.1.1
Power and current ratings (Derating for switching
Table 2-1 200V Drive ratings (200V to 240V ±10%)
Model
Maximum continuous
output current
Nominal power
at 220V
Motor power
at 230V
Peak current
A
kW
hp
A
1201
5.2
1.1
1.5
5.7
1202
6.8
1.5
2.0
7.4
1203
9.6
2.2
3.0
10.5
1204
11
3.0
3.0
12.1
2201
15.5
4.0
5.0
17.0
2202
22
5.5
7.5
24.2
2203
28
7.5
10
30.8
3201
42
11
15
46
3202
54
15
20
59
4201
68
18.5
25
74
4202
80
22
30
88
4203
104
30
40
114
5201
130
37
50
143
5202
154
45
60
169