The BA keypad cannot be installed on the front of the E12/E66 drive but
can be connected remotely via a serial cable to the external RJ 45
connector (see Figure 3-17 below for location of the RJ 45 connector).
Figure 3-17 location of external RJ 45 connector
The serial cable must be a shielded RJ45 cable with an appropriate
connector (suitable for mating with a Bulgin Buccaneer PX0833), rated
to a minimum of IP66. The maximum cable length is 30 metres.
If a cable is not connected then the connector cap must be installed as
shown in Figure 3-18.
Figure 3-18 RJ 45 connector with cap installed
NOTE