Figure 4-4 Size 4, 5 and 6 power connections
.
** See section 4.5
on page 71 for more information.
4.1.2 Ground connections
Size 1
On a size 1, the supply and motor ground connections are made using
the studs located either side of the drive near the plug-in power
connector. Refer to Figure 4-1 on page 66.
Size 2
On a size 2, the supply and motor ground connections are made using
the grounding bridge that locates at the bottom of the drive. See Figure
4-5 for details.
Size 3
On a size 3, the supply and motor ground connections are made using
an M6 nut and bolt that locates in the fork protruding from the heatsink
between the AC supply and motor output terminals. See Figure 4-6 for
details.
Size 4, 5 and 6
On a size 4, 5 and 6, the supply and motor ground connections are
made using an M10 bolt at the top (supply) and bottom (motor) of the
drive. See Figure 4-7 on page 69.
The supply ground and motor ground connections to the drive are
connected internally by a copper conductor with a cross-sectional area
given below:
Size 4: 19.2mm
2
(0.03in
2
, or slightly bigger than 6 AWG)
Size 5: 60mm
2
(0.09in
2
, or slightly bigger than 1 AWG)
Size 6: 75mm
2
(0.12in
2
, or slightly bigger than 2/0 AWG)
This connection is sufficient to provide the ground (equipotential
bonding) connection for the motor circuit under the following conditions:
If the necessary conditions are not met, an additional ground connection
must be provided to link the motor circuit ground and the supply ground.
U
V
W
Motor
Optional ground
connection
+DC
BR
Thermal
overload
protection
device
Output connections
Input connections
Mains
Supply
L1
L2
Optional
line reactor
Optional
EMC filter
Fuses
L3
L1
L2
L3
+DC -DC
Internal
EMC filter
PE
Supply
ground
*
*
4 5 6
Size 6 only:
Heatsink
fan supply
connections
**
Electrochemical corrosion of earthing terminals
Ensure that grounding terminals are protected against
corrosion i.e. as could be caused by condensation.
To standard
Conditions
IEC 60204-1 &
EN 60204-1
Supply phase conductors having cross-sectional area
not exceeding:
Size 4: 38.4mm
2
Size 5: 120mm
2
Size 6: 150mm
2
NFPA 79
Supply protection device rating not exceeding:
Size 4: 200A
Size 5: 600A
Size 6: 1000A
WARNING