Safety
Information
Product
Information
Mechanical
Installation
Electrical
Installation
Getting
Started
Basic
parameters
Running
the motor
Optimization
SMARTCARD
operation
PC tools
Advanced
parameters
Technical
Data
Diagnostics
UL Listing
Information
254
Affinity User Guide
www.controltechniques.com Issue Number: 5
It.AC
Output current overload timed out (I
2
t) - accumulator value can be seen in Pr 4.19
20
Ensure the load is not jammed / sticking
Check the load on the motor has not changed
Ensure rated speed parameter is correct (RFC)
Ensure that the motor rated current is not set to zero
It.br
Braking resistor overload timed out (I
2
t) – accumulator value can be seen in Pr 10.39
19
Ensure the values entered in Pr
10.30
and Pr
10.31
are correct
Increase the power rating of the braking resistor and change Pr
10.30
and Pr
10.31
If an external thermal protection device is being used and the braking resistor software overload is not required, set Pr
10.30
or
Pr
10.31
to 0 to disable the trip
LOAD
Low load detected
38
Check mechanical motor coupling
O.CtL
Drive control board over temperature
23
Check enclosure / drive fans are still functioning correctly
Check enclosure ventilation paths
Check enclosure door filters
Check ambient temperature
Reduce drive switching frequency
O.ht1
Power device over temperature based on thermal model
21
Reduce drive switching frequency
Reduce duty cycle
Decrease acceleration / deceleration rates
Reduce motor load
O.ht2
Heatsink over temperature
22
Check enclosure / drive fans are still functioning correctly
Check enclosure ventilation paths
Check enclosure door filters
Increase ventilation
Decrease acceleration / deceleration rates
Reduce drive switching frequency
Reduce duty cycle
Reduce motor load
Oht2.P
Power module heatsink over temperature
105
Check enclosure / drive fans are still functioning correctly
Check enclosure ventilation paths
Check enclosure door filters
Increase ventilation
Decrease acceleration / deceleration rates
Reduce drive switching frequency
Reduce duty cycle
Reduce motor load
O.ht3
Drive over-temperature based on thermal model
27
The drive will attempt to stop the motor before tripping. If the motor does not stop in 10s the drive trips immediately.
Check DC bus ripple
Reduce duty cycle
Reduce motor load
Oht4.P
Power module rectifier over temperature or input snubber resistor over temperature (size 4 and above)
102
Check for supply imbalance
Check for supply disturbance such as notching from a DC drive
Check enclosure / drive fans are still functioning correctly
Check enclosure ventilation paths
Check enclosure door filters
Increase ventilation
Decrease acceleration / deceleration rates
Reduce drive switching frequency
Reduce duty cycle
Reduce motor load
Trip
Diagnosis
Содержание Affinity
Страница 274: ...0474 0000 05 ...