Safety
Information
Product
Information
Mechanical
Installation
Electrical
Installation
Getting
Started
Basic
parameters
Running
the motor
Optimization
SMARTCARD
operation
PC tools
Advanced
parameters
Technical
Data
Diagnostics
UL Listing
Information
Affinity User Guide
223
Issue Number: 5 www.controltechniques.com
The following table shows the voltage levels used by drives with each
voltage rating.
* Vml
1
is defined by Pr
6.48
. The values in the table above are the
default values.
The line power supply loss detection level can be adjusted using this
parameter. If the value is reduced below the default value, the default
value is used by the drive. If the level is set too high, so that the line
power supply loss detection becomes active under normal operating
conditions, the motor will coast to a stop.
Open-loop
These parameters control the proportional and integral gains of the
current controller used in the open loop drive. As already mentioned the
current controller either provides current limits or closed loop torque
control by modifying the drive output frequency. The control loop is also
used in its torque mode during line power supply loss, or when the
controlled mode standard ramp is active and the drive is decelerating, to
regulate the flow of current into the drive. Although the default settings
have been chosen to give suitable gains for less demanding applications
it may be necessary for the user to adjust the performance of the
controller. The following is a guide to setting the gains for different
applications.
Current limit operation:
The current limits will normally operate with an integral term only,
particularly below the point where field weakening begins. The
proportional term is inherent in the loop. The integral term must be
increased enough to counter the effect of the ramp which is still
active even in current limit. For example, if the drive is operating at
constant frequency and is overloaded the current limit system will try
to reduce the output frequency to reduce the load. At the same time
the ramp will try to increase the frequency back up to the demand
level. If the integral gain is increased too far the first signs of
instability will occur when operating around the point where field
weakening begins. These oscillations can be reduced by increasing
the proportional gain. A system has been included to prevent
regulation because of the opposite actions of the ramps and the
current limit. This can reduce the actual level that the current limit
becomes active by 12.5%. This still allows the current to increase up
to the current limit set by the user. However the current limit flag
(Pr
10.09
) could become active up to 12.5% below the current limit
depending on the ramp rate used.
Torque control:
Again the controller will normally operate with an integral term only,
particularly below the point where field weakening begins. The first
signs of instability will appear around base speed, and can be
reduced by increasing the proportional gain. The controller can be
less stable in torque control mode rather than when it is used for
current limiting. This is because load helps to stabilise the controller,
and under torque control the drive may operate with light load.
Under current limit the drive is often under heavy load unless the
current limits are set at a low level.
Line power supply loss and controlled standard ramp:
The DC bus voltage controller becomes active if line power supply
loss detection is enabled and the drive supply is lost or controlled
standard ramp is being used and the machine is regenerating. The
DC bus controller attempts to hold the DC bus voltage at a fixed
level by controlling the flow of current from the drive inverter into its
DC bus capacitors.
The output of the DC bus controller is a current demand which is fed
into the current PI controller as shown in the following diagram.
Although it is not usually necessary the DC bus voltage controller
can be adjusted with Pr
5.31
. However, it may often be necessary to
adjust the current controller gains to obtain the required
performance. If the gains are not suitable it is best to set up the drive
in torque control first. Set the gains to a value that does not cause
instability around the point at which field weakening occurs. Then
revert back to open loop speed control in standard ramp mode. To
test the controller the supply should be removed while the motor is
running. It is likely that the gains can be increased further if required
because the DC bus voltage controller has a stabilising effect,
provided that the drive is not required to operate in torque control
mode.
RFC
The Kp and Ki gains are used in the voltage based current controller.
The default values give satisfactory operation with most motors.
However it may be necessary to change the gains to improve the
performance. The proportional gain (Pr
4.13
) is the most critical value in
controlling the performance. Either the value can be set by auto-tuning
(see Pr
5.12
) or it can be set by the user so that
Pr
4.13
= Kp = (L / T) x (I
fs
/ V
fs
) x (256 / 5)
Where:
T is the sample time of the current controllers. The drive
compensates for any change of sample time, and so it should be
assumed that the sample time is equivalent to the lowest sample
rate of 167
μ
s.
L is the motor inductance. For an induction motor this is the per
phase transient inductance (
σ
L
s
). This is the inductance value stored
in Pr
5.24
after the autotune test is carried out.
Voltage level
200V drive
400V drive
575V drive
690V drive
Vuu
175
330
435
Vml
1
205*
410*
540*
Vml
2
Vml
1
- 10V
Vml
1
- 20V
Vml
1
- 25V
Vml
3
Vml
1
+ 10V
Vml
1
+ 15V
Vml
1
+ 50V
Vuu Restart
215
425
590
6.48
Line power supply loss ride through detection level
RW
Uni
RA
US
Ú
0 to
DC_VOLTAGE_SET_MAX V
Ö
200V drive: 205
400V drive: 410
575V drive: 540
690V drive: 540
4.13
Current loop P gain
RW
Uni
US
OL
Ú
0 to 30,000
Ö
All voltage ratings: 20
RFC
Ú
Ö
200V drive: 75
400V drive: 150
575V drive: 180
690V drive: 215
4.14
Current loop I gain
RW
Uni
US
OL
Ú
0 to 30,000
Ö
All voltage ratings: 40
RFC
Ú
Ö
200V drive: 1,000
400V drive: 2,000
575V drive: 2,400
690V drive: 3,000
DC bus
voltage
controller
P Pr
4.13
I Pr
4.14
Frequency
reference
Active current
DC bus
capacitor
Current
demand
Содержание Affinity
Страница 274: ...0474 0000 05 ...