Building automation interface: Module has detected a fault
212
Check value in Pr
17.50
. The following table lists the possible error codes.
SLX.HF
Solutions Module slot X trip: Solutions Module X hardware fault
200,205
Ensure Solutions Module is installed correctly
Return Solutions Module to supplier
SL3.HF
Building automation interface: Module hardware fault
210
Ensure Solutions Module is installed correctly
Return Solutions Module to supplier
SLX.nF
Solutions Module slot X trip: Solutions Module has been removed
203,208
Ensure Solutions Module is installed correctly
Reinstall Solutions Module
Save parameters and reset drive
SL3.nF
Building automation interface: Module has been removed
213
Ensure Solutions Module is installed correctly
Reinstall Solutions Module
Save parameters and reset drive
SL.rtd
Solutions Module trip: Drive mode has changed and Solutions Module parameter routing is now incorrect
215
Press reset.
If the trip persists, contact the supplier of the drive.
SLX.tO
Solutions Module slot X trip: Solutions Module watchdog timeout
201,206
Press reset.
If the trip persists, contact the supplier of the drive.
SL3.tO
Building automation interface: Module watchdog timeout
211
Press reset.
If the trip persists, contact the supplier of the drive.
t040 to t089
User defined trip
40 to 89
Onboard PLC program must be interrogated to find the cause of this trip
t099
User defined trip
99
Onboard PLC program must be interrogated to find the cause of this trip
t101
User defined trip
101
Onboard PLC program must be interrogated to find the cause of this trip
t112 to t160
User defined trip
112 to 160
Onboard PLC program must be interrogated to find the cause of this trip
t168 to t174
User defined trip
168 to 174
Onboard PLC program must be interrogated to find the cause of this trip
t216
User defined trip
216
Onboard PLC program must be interrogated to find the cause of this trip
th
Motor thermistor trip
24
Check motor temperature
Check thermistor continuity
Set Pr
7.15
= VOLt and reset the drive to disable this function
thS
Motor thermistor short circuit
25
Check motor thermistor wiring
Replace motor / motor thermistor
Set Pr
7.15
= VOLt and reset the drive to disable this function
Trip
Diagnosis
Error code
Trip Description
0
No trip
10
Module operating system error
20
Real time clock error
30
IP54 cooling fan power supply fault
40
Drive to Solutions Module interface error
50
Building automation network error