15
Transfer protocol
Actuators KNX S4-B10, KNX S2-B6 and KNX S1-B2 230 V
Status: 18.04.2017 • Technical changes and errors excepted.
3.
Transfer protocol
3.1. List of all communication objects
Abbreviations:
R
Read
W Write
C
Communication
T
Transfer
No.
Name
Function
Flags
Data Point Type
Size
1
Software version
Readable
R-C-
[217.1] DPT_Version
2 Bytes
Only KNX S4-B10 and KNX S2-B6
50
Input 1 long term
Input /
output
RWCT
[1.8] DPT_UpDown
1 Bit
51
Input 1 short term
Output
R-CT
[1.8] DPT_UpDown
1 Bit
52
Input 1 switching
Input /
output
RWCT
[1.1] DPT_Switch
1 Bit
53
Input 1 dim relative
Input /
output
RWCT
[3.7]
DPT_Control_Dimm
ing
4 Bit
54
Input 1 encoder 8 bit
Output
R-CT
[5] 5.xxx
1 Byte
55
Input 1 encoder
temperature
Output
R-CT
[9.1]
DPT_Value_Temp
2 Bytes
56
Input 1 encoder brightness
Output
R-CT
[9.4]
DPT_Value_Lux
2 Bytes
57
Input 1 scene
Output
R-CT
[18.1]
DPT_SceneControl
1 Byte
58
Input 1 blocking object
Input
RWC-
[1.1] DPT_Switch
1 Bit
60
Input 2 long term
Input /
output
RWCT
[1.8] DPT_UpDown
1 Bit
61
Input 2 short term
Output
R-CT
[1.8] DPT_UpDown
1 Bit
62
Input 2 switching
Input /
output
RWCT
[1.1] DPT_Switch
1 Bit
63
Input 2 dim relative
Input /
output
RWCT
[3.7]
DPT_Control_Dimm
ing
4 Bit
64
Input 2 encoder 8 bit
Output
R-CT
[5] 5.xxx
1 Byte
65
Input 2 encoder
temperature
Output
R-CT
[9.1]
DPT_Value_Temp
2 Bytes
66
Input 2 encoder brightness
Output
R-CT
[9.4]
DPT_Value_Lux
2 Bytes
67
Input 2 scene
Output
R-CT
[18.1]
DPT_SceneControl
1 Byte
Содержание KNX S1-B2 230 V