58
Parameter setting
Actuators KNX S4-B10, KNX S2-B6 and KNX S1-B2 230 V
Status: 18.04.2017 • Technical changes and errors excepted.
Threshold value per parameter:
Set the threshold value and delay times for shading (prevents constant opening and
closing when light conditions change quickly).
Threshold value per communication object:
The threshold value is received via the communication object and can be changed ad-
ditionally (e.g. button for "more sensitive" and "less sensitive"). Set the delay times for
shading here (prevents constant opening and closing when light conditions change
quickly).
Position of the sun:
------------------------------
Defining position of sun via values:
Enter the range (direction and height) in which the sun must be located for the shading
to be active.
Shading threshold specification per
Parameter
Shading threshold value in klux
0 … 100; 30
Drive up delay in min
0 … 255; 12
Drive down delay in min
0 … 30; 1
Send current shading status
No • Yes
Shading threshold specification per
communication object
The value communicated last shall be
retained
• not
• after voltage returns
• after voltage returns and programming
Start threshold value in klux
valid until 1st communication
0 … 100; 30
Type of limit value change
• Absolute value with a 16bit comm. object
• Lifting/lowering with a comm. object
• Lifting/lowering with two comm. objects
Increments in klux
(only when "lifting/lowering with comm.
object")
1 … 5; 2
Drive up delay in min
0 … 255; 12
Drive down delay in min
0 … 30; 1
Send current shading status
no • yes
Assess position of the sun
no • yes
Assess position of the sun
yes
Position of the sun is defined via
• Discreet value of azimuth and elevation
• Directions
(regarding azimuth and elevation)
Position of the sun is defined via
discreet value
of azimuth and elevation
Azimuth from
0 … 360