71
General part
Actuators KNX S4-B10, KNX S2-B6 and KNX S1-B2 230 V
Status: 18.04.2017 • Technical changes and errors excepted.
If the drive is to be moved a bit farther, then a little longer push is needed (longer than
time 1 but shorter than time 1+2). The drive stops immediately when releasing the but-
ton.
If the drive must be moved independently into the end position, the button is released
only after times 1 + 2 have expired. The move can be stopped by briefly pushing.
Dead man's switch:
The drive moves as soon as the button is pushed and stops as soon as the button is
released.
5.1.2. Connection option for zero position sensors
See also section
Movement Range Limit
in chapter
Control (drives)
, page 47. The ex-
amples and the communication object numbers refer to the mutual master-slave cou-
pling of drives at the output channel A and channel B.
Point in time 0:
Push of button, start of time 1
Release before time 1 expired:
step (or stop if drive is moving)
Point in time 1:
End of time 1, start of time 2
Moving command
Release after time 1 expired
but before time 2 expires:
Stop
Release after time 1 + 2 expired:
Move into end position
Control mode
Comfort mode
Behavior during button operation:
Button is pushed and
released before time 1 expired = stop/step
held longer than time 1 = Up or Down
released between time 1 and 1-2= stop
released after time 1 +2 = no more stop
Time 1
0.0s ... • 2 s; 0.4 s
Time 2
0 s • 2 s; 2 s
Control mode
Dead man's switch
Behavior during button operation:
Push button = Up or Down command
Release button = Stop command
Time 1
Time 2
0
1
1 + 2
Abb. 1
Time interval comfort mode diagram