17
Transfer protocol
Actuators KNX S4-B10, KNX S2-B6 and KNX S1-B2 230 V
Status: 18.04.2017 • Technical changes and errors excepted.
124
Channel A call saving
scenes
Input
RWC-
[18.1]
DPT_SceneControl
1 Byte
125
Channel A outdoor
temperature
Blocking object
Input
RWC-
[1.1] DPT_Switch
1 Bit
126
Channel A outdoor
temperature blocking
measurement value
Input
RWC-
[9.1]
DPT_Value_Temp
2 Bytes
127
Channel A outdoor
temperature blocking status
Output
R-CT
[1.1] DPT_Switch
1 Bit
128
Channel A twilight object
Input
RWC-
[1.1] DPT_Switch
1 Bit
129
Channel A twilight
measurement value
Input
RWC-
[9.4]
DPT_Value_Lux
2 Bytes
130
Channel A twilight status
Output
R-CT
[1.1] DPT_Switch
1 Bit
131
Channel A time control
Input
RWC-
[1.1] DPT_Switch
1 Bit
132
Channel A inside
temperature release object
Input
RWC-
[1.1] DPT_Switch
1 Bit
133
Channel A inside
temperature release
measurement value
Input
RWC-
[9.1]
DPT_Value_Temp
2 Bytes
134
Channel A inside
temperature release target
value
Input
RWC-
[9.1]
DPT_Value_Temp
2 Bytes
135
Channel A inside
temperature release status
Output
R-CT
[1.1] DPT_Switch
1 Bit
136
Channel A shading object
Input
RWC-
[1.1] DPT_Switch
1 Bit
137
Channel A shading
brightness
Measurement value 1
Input
RWC-
[9.4]
DPT_Value_Lux
2 Bytes
138
Channel A shading
brightness
Measurement value 2
Input
RWC-
[9.4]
DPT_Value_Lux
2 Bytes
139
Channel A shading
brightness
Measurement value 3
Input
RWC-
[9.4]
DPT_Value_Lux
2 Bytes
140
Channel A shading
threshold value
Input /
output
RWCT
[9.4]
DPT_Value_Lux
2 Bytes
141
Channel A shading
threshold value 1 = + | 0 = -
Input
RWC-
[1] 1.xxx
1 Bit
142
Channel A shading
threshold value +
Input
RWC-
[1] 1.xxx
1 Bit
143
Channel A shading
threshold value -
Input
RWC-
[1] 1.xxx
1 Bit
144
Channel A shading status
Output
R-CT
[1.1] DPT_Switch
1 Bit
No.
Name
Function
Flags
Data Point Type
Size