Transfer protocol
Actuators KNX S4-B10, KNX S2-B6 and KNX S1-B2 230 V
Status: 18.04.2017 • Technical changes and errors excepted.
352
Channel B warm air supply
blocking object
Input
RWC-
[1.1] DPT_Switch
1 Bit
353
Channel B warm air supply
inside temperature
measurement value
Input
RWC-
[9.1]
DPT_Value_Temp
2 Bytes
354
Channel B warm air supply
Outside temperature
measurement value
Input
RWC-
[9.1]
DPT_Value_Temp
2 Bytes
355
Channel B warm air supply
blocking target value
Input
RWC-
[9.1]
DPT_Value_Temp
2 Bytes
356
Channel B warm air supply
blocking status
Output
R-CT
[1.1] DPT_Switch
1 Bit
357
Channel B inside
temperature opening object
Input
RWC-
[1.1] DPT_Switch
1 Bit
358
Channel B inside
temperature opening
measurement value
Input
RWC-
[9.1]
DPT_Value_Temp
2 Bytes
359
Channel B inside
temperature opening target
value
Input
RWC-
[9.1]
DPT_Value_Temp
2 Bytes
360
Channel B inside
temperature opening
threshold value
Input
output
RWCT
[9.1]
DPT_Value_Temp
2 Bytes
361
Channel B inside
temperature opening
threshold value
1 = +
Input
RWC-
[1] 1.xxx
1 Bit
362
Channel B inside
temperature opening
threshold value +
Input
RWC-
[1] 1.xxx
1 Bit
363
Channel B inside
temperature opening
threshold value-
Input
RWC-
[1] 1.xxx
1 Bit
364
Channel B inside
temperature opening status
Output
R-CT
[1.1] DPT_Switch
1 Bit
365
Channel B inside humidity
opening object
Input
RWC-
[1.1] DPT_Switch
1 Bit
366
Channel B inside humidity
opening
Measurement value
Input
RWC-
[9.7]
DPT_Value_Humidit
y
2 Bytes
367
Channel B inside opening
status
Output
R-CT
[1.1] DPT_Switch
1 Bit
370
Channel B zero position
reached
Input
RWC-
[1.1] DPT_Switch
1 Bit
371
Channel B zero position
sensor malfunctioning
Output
R-CT
[1.1] DPT_Switch
1 Bit
No.
Name
Function
Flags
Data Point Type
Size