12
Installation and start-up
Actuators KNX S4-B10, KNX S2-B6 and KNX S1-B2 230 V
Status: 18.04.2017 • Technical changes and errors excepted.
2.2.5. Status display by the channel LEDs
2.3. Notes on mounting and commissioning
Device must not be exposed to water (rain). This could result in the electronic being
damaged. A relative air humidity of 95% must not be exceeded. Avoid bedewing.
After the operating voltage has been applied, the device will enter an initialisation pha-
se lasting a few seconds. During this phase no information can be received or sent via
the bus.
For KNX devices with safety functions (e.g. wind or rain blocks), periodical monitoring
of the safety objects must be set up. The optimal ratio is 1:3 (example: if the weather
station sends a value every 5 minutes, the actuator must be configured for a monitor-
ing period of 15 minutes).
Behaviour LED
To
top
Drive in top end position/device on.
To
bottom
Drive in bottom end position/drive on.
Flashes slowly
top
Drive moves up.
Flashes slowly
bottom
Drive moves down.
Flashes
quickly
top
Drive in top end position, blocking active.
Flashes
quickly
bottom
Drive in bottom position, blocking active.
Flashes
quickly
both
simultaneously
Drive in intermediate position, blocking active.
Extend
both
Drive in intermediate position.
Flashes
both alternately
Automatic runtime determination error.
If the drive can be moved, drive it into the end
position by hand (drive in/drive out
completely or open/close) in order to restart
the runtime determination.
If the drive cannot be moved, check the
connections.
"Runlight"
above all LEDs
all channels
Incorrect application version was loaded. Use
the version compatible with the device!