74
General part
Actuators KNX S4-B10, KNX S2-B6 and KNX S1-B2 230 V
Status: 18.04.2017 • Technical changes and errors excepted.
5.2. Output channel with switch function
5.2.1. Correlation connection – time switch – block
Application 1: Staircase light at channel A1, that can only be switchable at twilight/
night (linking) and that is turned on during a fire alarm (blocking).
When switching via communication object "Channel A1 switch" (200), the light is
turned on or off normally. When switching via object "Channel A1 staircase light func-
tion start" (205), the staircase light time function is activated. The time function has pri-
ority, i.e. the status triggered by normal switching is overwritten.
200: Channel A1
Switching
with stair-
205: Channel A1
Switching
Input
Staircase light funct. Start
case light
209: Channel A1
Linking
Input
(from twilight sensor)
AND
Linking
203: Channel A1
Blocking object
input
(from smoke detector)
Block
201: Channel A1
Feedback
Output
Relay
function
function