Parameter setting
Actuators KNX S4-B10, KNX S2-B6 and KNX S1-B2 230 V
Status: 18.04.2017 • Technical changes and errors excepted.
Shading is allowed
if the measurement value is larger than the threshold value+hysteresis
and blocked
if the measurement value is smaller than or equal to the threshold value.
Twilight/time control:
The time control is provided via a communication object. The input object "twilight
control" is linked with the output object of a brightness sensor. A 1bit object (smaller
or larger than a threshold value), as well as a 16bit object (measurement value) can be
used for the twilight control.
16 bit input object:
Indoor temperature release:
The input object "indoor temperature release" is linked with the output object of a tem-
perature sensor. The input object can be a 1bit object (smaller or larger than a th-
reshold value), as well as a 16bit object (measurement value or target and actual
value).
16 bit input object:
Hysteresis in 0.1°C
1 … 100; 20
Send current blocking status
no • yes
Use twilight/time control
• no
• only twilight control
• only time control
• both (OR linking)
Use twilight/time control
only twilight control / both
Type of twilight object
1 bit • 16 bit
Type of twilight object
16 bit
Twilight threshold value in lux
1 … 1000; 10
Switching delay
1 minute
Send current twilight status
no • yes
Use inside temperature release
no • yes
Type of input object
1 bit • 16 bit • 16 bit target/actual
temperature
Type of input object
16 bit
Threshold value in 0.1°C
-300 … 800; 200
Hysteresis in 0.1°C
1 … 100; 20
Send current blocking status
no • yes