60
Parameter setting
Actuators KNX S4-B10, KNX S2-B6 and KNX S1-B2 230 V
Status: 18.04.2017 • Technical changes and errors excepted.
Moving position (for awnings and blinds):
------------------------------
Use teaching object for new shading position
: The curtain position it can be spe-
cified numerically or taught manually. For teaching set "use teaching object: Yes" and
the "channel X shading position teaching object" is used for saving the position rea-
ched. Saving occurs for value = 1 and can for example be realized via a button linked
to the teaching object. Numerical specifications already set are overwritten by the tea-
ching object.
4.3.1.5.Automatic for windows (drives)
The menu item "Automatic" only appears if internal automatic is selected for "Control".
Depending on the setting, the internal automatic functions take the outdoor tempera-
ture, indoor temperature and room air humidity into account, and allow forced venti-
lation via a communication object.
In order to fully utilize the internal ventilation automatic, information about the outdoor
and indoor temperature and the inside air humidity must be present in the bus system.
Cold supply air lock:
The input object "cold supply air block" is linked with the output object of a tempera-
ture sensor. The input object can be a 1bit object (smaller or larger than a threshold
value), as well as a 16bit object (measurement value).
1bit input object:
Ventilation is allowed if the bit is 0 and blocked if the bit is 1.
16bit input object:
Ventilation is allowed if the measurement value is larger than the threshold value+hys-
teresis
and blocked if the measurement value is smaller than or equal to the threshold value.
Awning position in % or
blind position in %
0 … 100; 75
Use teaching object for new shading
position
no • yes
Use cold supply air block
no • yes
Use cold supply air block
yes
Type of temperature input object
1 bit • 16 bit
Type of temperature input object
1 bit
Type of temperature input object
16 bit
Threshold value in 0.1°C
-300 … 800; 50
Hysteresis in 0.1°C
1 … 100; 20
Send current blocking status
no • yes