44
Parameter setting
Actuators KNX S4-B10, KNX S2-B6 and KNX S1-B2 230 V
Status: 18.04.2017 • Technical changes and errors excepted.
Input for scene control:
If scenes are called and saved with the input, then choose the "Scenes" bus function
and specify the saving, time difference (call/save) and scene number.
The input can be blocked using a blocking object. For active blocking there is
no bus
communication
.
4.3. Outputs
State here what is connected to the individual output channels.
Thereafter, the setting options for the individual outputs will appear:
Settings for drives (channel A, B, C, D):
•
General specifications for the connected drive
(see
Channel settings – drives
, page 45)
•
Control functions: Movement range limit, blocking, type of automatic
(see
Control (drives)
, page 47)
•
Automatic functions: Automatic can be specified externally or internally
(see
Automatic - internal for shading (drives)
, page 55 or
Automatic for
windows (drives)
, page 60)
•
Scenes: Movement positions (see
Scenes (drives)
, page 64)
•
Button inputs: Configuration as actuator button, bust button or for zero position
sensor (see
Button inputs (drives)
, page 64)
Settings for switch functions
(Channels are divided into two switches A1|A2, B1|B2, C1|C2, D1|D2):
•
General specifications for the switch function
(see
Channel settings – switch functions
, page 65)
•
Connecting different communication objects
(see
Connection (switch functions)
, page 66)
Function
Scenes
Button operation
• without saving
• with saving
Time between calling and saving in 0.1
seconds
(only if selected "with saving")
1...50; 10
Scene No.
0...127
Use blocking object
No • Yes
Operating mode
Channel A / B / C / D controls
• shutter
• blind
• awning
• window
• double switch function