1 Rapid Link 5 system
1.5 Compliance with UL standards
24
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
sensing is accomplished by monitoring the DC bus and/or all the motor outputs.
These drives or control units have not been evaluated as providing a safety or limiting feature.
The devices use the supplied thermocouple in the IGBT packs to control thermal functions – 100 % production test
used to confirm functionality.
These devices are for installation in Overvoltage Category III and pollution degree 3.
Auxiliary Control outputs intended to drive resistant Load.
Marking (continued):
75 °C wire only
“Use copper conductors only”
Short Circuit Current Ratings:
“Suitable for use on a circuit capable of delivering not more than 100 000 rms symmetrical amperes, 480 volts
maximum. Suitable for motor group installation. When protected by J class fuses rated 30A.”
“Suitable for use on a circuit capable of delivering not more than 10 000 rms symmetrical amperes, 480 volts
maximum. Suitable for motor group installation. When protected by circuit breaker having an interrupting rating not
less than 10 000 rms symmetrical amperes, 480 volts maximum, rated 32A.”
“Suitable for use on a circuit capable of delivering not more than 65 000 rms symmetrical amperes, 480 volts
maximum. When protected by Type E combination motor controller model PKZM4-32 manufactured by Eaton rated
480Y/277Vac 20HP.”
RASP…R (disconnect switch):
“Suitable for use on a circuit capable of delivering not more than 10 000 rms symmetrical amperes, 480 volts
maximum. Suitable for motor group installation. When protected by J class fuses rated 30A.”
“Suitable for use on a circuit capable of delivering not more than 10 000 rms symmetrical amperes, 480 volts
maximum. Suitable for motor group installation. When protected by circuit breaker having an interrupting rating not
less than 10 000 rms symmetrical amperes, 480 volts maximum, rated 32A.”
“Suitable for use on a circuit capable of delivering not more than 10 000 rms symmetrical amperes, 480 volts
maximum. When protected by Type E combination motor controller model PKZM4-32 manufactured by Eaton rated
480Y/277Vac 20HP.”
75 °C wire only
“Use copper conductors only”
Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must
be provided in accordance with the National Electrical Code and any additional local codes or the equivalent.
UL61800-5-1
WARNING
The opening of the branch circuit protective device may be an indication that a fault has been interrupted. To
reduce the risk of fire or electric shock, current-caring parts and other components of the controller should be
examined and replaced if damaged.
CSA C22.2 No. 274
ATTENTION
THE OPENING OF THE BRANCH CIRCUIT PROTECTIVE DEVICE MAY BE AN INDICATION
THAT A FAULT HAS BEEN INTERRUPTED. TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, CURRENT-CARING
PARTS AND OTHER COMPONENTS OF THE CONTROLLER SHOULD BE EXAMINED AND REPLACED IF
APPROPRIATE. IF BURNOUT OF THE CURRENT ELEMENT OF AN OVERLOAD RELAY OCCURS, THE COMPLETE
OVERLOAD RELAY MUST BE REPLACED
All models incorporate internal overload protection for the motor load that does not require the use of an external
or remote overload protection device. The protection level is adjustable and the method of adjustment is provided
within instructions/manual for the product.
Shall be marked with Motor overload protection limit set at 150 % of FLA.
Содержание Rapid Link 5
Страница 1: ...Manual Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN ...
Страница 4: ...II ...
Страница 38: ...1 Rapid Link 5 system 1 10 Service and warranty 34 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 118: ...3 Installation 3 7 Isolation test 114 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 196: ...8 Parameter list 8 4 Parameter groups for RASP5 192 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 246: ...10 Error Messages 10 2 Error Messages 242 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...