8 Parameter list
8.3 Parameter groups for RAMO5
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
169
8.3.2 Parameter group 1 (Basic)
Table 35:
Parameter group 1 (Basic)
Parameter
Designation
Description
Unit
Min
Max
DS
P1-08
Motor Nom Current
Motor rated Current
By setting the “Motor Nom Current” in the drive, the
motor overload protection is configured to match the
motor rating.
When the measured motor current exceeds “Motor
Nom Current”, the decimal points on the display will
flash to indicate an overload condition.
If this condition persists, the drive will eventually trip,
displaying
I.t-trP
, preventing thermal overload of
the motor.
Amps
0.3
6.6
6.6
P1-13
SEN Config Select
Configuration of sensor inputs with a fix set of combi-
nations
–
1
4
1
P1-14
Access key
Entry of the password to get access to the extended
parameter set.
The value to be put in is determined by the level to be
accessed.
Level 2 (access to parameter groups 0 to 8):
P1-14 = P2-32 (factory setting: 101)
–
0
65535
0
Содержание Rapid Link 5
Страница 1: ...Manual Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN ...
Страница 4: ...II ...
Страница 38: ...1 Rapid Link 5 system 1 10 Service and warranty 34 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 118: ...3 Installation 3 7 Isolation test 114 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 196: ...8 Parameter list 8 4 Parameter groups for RASP5 192 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 246: ...10 Error Messages 10 2 Error Messages 242 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...