1 Rapid Link 5 system
1.4 Technical data
20
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
Main circuit
Feeder unit
Rated operational voltage
U
e
V
3 AC 400/480
3 AC 400/480
Rated voltage for brake control
U
e
V
180/207 V DC
230/277 V AC
400/480 V AC
180/207 V DC
230/277 V AC
400/480 V AC
Voltage range
U
LN
V
380 - 10% - 480 + 10%
380 - 10% - 480 + 10%
Frequency range
f
LN
Hz
(50 - 10 %) - (60 + 10 %)
50/60 (45–66 Hz ±0 %)
Network configuration
Alternating voltage, center-point-
earthed star network (TN-S network)
Phase-earthed AC supply systems are
not permitted.
Alternating voltage, center-point-
earthed star network (TN-S network)
Phase-earthed AC supply systems are
not permitted.
Mains switch-on frequency
Quantity
–
At least one minute pause between
two power-up operations
Mains current
THD
%
< 120
< 120
Short-circuit current
I
K
kA
< 10
< 10
Short-circuit protection device
(Power bus incoming unit)
PKE3/XTUCP-36
FAZ-3-B20 or FAZ-3-C20
PKE3/XTUCP-36
FAZ-3-B20 or FAZ-3-C20
Overvoltage category/
Degree of pollution (DIN/VDE 0110)
III
III
Rated impulse withstand voltage
U
imp
kV
4
–
Leakage current to PE earth (EN 50178)
I
PE
mA
< 3.5
< 3.5
Power section
Instance
RAMO5-D: Direct-on-line starter with
thyristors and bypass contacts
Frequency inverter with internal DC-
Link and IGBT inverter
RAMO5-W: Reversing starter with
relay, thyristors and bypass contacts
two-phase controlled
Service life (AC3)
Quantity
> 10 millions connections
–
Output voltage
U
2
V AC
U
LN
0 - U
LN
Output frequency
f
2
Hz
50/60 Hz
0 - 50 Hz, max. 500 Hz
Rated current
I
e
A
6.6
2.4 / 4.3 / 5.6 / 8.5
Load current for the control unit for an
external brake
I
A
≦
0.6
600 mA constant, 6 A for 120 ms
≦
0.6
600 mA constant, 6 A for 120 ms
Adjustable motor protection
I
A
0.3 - 6.6
0.48 - 8.5
Overload withstand capability
for 60 s every 600 s at +40
°
C
I
L
%
–
150
for 2 s every 20 s at +40
°
C
I
H
%
–
200
Allocated motor output
1)
(with motor protection) with 400 V,
50 Hz
P
kW
0.09 - 3
0.18 - 4
at 440 V - 460 V, 60 Hz
P
HP
0.125 - 3
0.25 - 5
Technical data
Formula
symbol
Unit
Value
RAMO5
RASP5
Содержание Rapid Link 5
Страница 1: ...Manual Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN ...
Страница 4: ...II ...
Страница 38: ...1 Rapid Link 5 system 1 10 Service and warranty 34 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 118: ...3 Installation 3 7 Isolation test 114 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 196: ...8 Parameter list 8 4 Parameter groups for RASP5 192 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 246: ...10 Error Messages 10 2 Error Messages 242 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...