2 Engineering
2.14 Regenerative braking
78
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
Table 14:
Braking chopper parameters
Table 15:
Technical data (applicable to all RASP5… devices)
Para-
meter
Designation
Description
Unit
Min
Max
DS
P4-05
Brake chopper mode
Parameter function only for devices
with internal brake resistors
0: Disabled
1: Active in RUN
2: Active in RUN and STOP
–
0
2
2
ATTENTION
When using RAMO5 or RASP5 units, do
not
connect external
brakes directly (to U, V, or W) in the motor's terminal box.
Size
Value
Resistance R
400
Ω
Tolerance
±20 %
Energy E
200 Ws
Power P
100 W
Isolation voltage V
t
4000 V
Maximum barrier layer temperature T
jmax
125 °C
Switch-on threshold for the braking transistor U
DC
to: 780 V DC
OFF 756 V DC