9 Communication
9.2 EtherNet / IP
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
223
NETReceivePDZ 2 – reference (RASP5 only)
The permissible values fall within a range of P1-02 (minimum frequency) to
P1-01 (maximum frequency).
This value will be scaled by a factor of 0.1 in the application.
NETReceivePDZ 3 – field bus ramp time (RASP5 only)
The acceptable values range from 0 to 3000 seconds.
The values are set using parameter P5-07. The enable is issued using para-
meter P5-04.
This value will be scaled by a factor of 0.01 in the application.
Example: 500
≙
5.00 s
NETReceivePDZ 4
NETReceivePDZ 4 has no function.