2 Engineering
2.9 Sensor inputs
64
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
The following sensors can be connected, for example:
•
optical (light barriers),
•
inductive (proximity switches),
•
mechanical (end switch).
The length of the sensor connection cables for inputs I1 and I2 is limited to
5 m. The sensors are supplied with 24 V DC from the RAMO5 and RASP5
Rapid Link modules. The total current of all sensors is limited to 160 mA.
The sensor supply is short-circuit proof. In the event of an overload or short-
circuit, a group fault signal will be generated and the
FLT
LED will light up red
to indicate this. As soon as the fault is fixed, the error message can be reset
with the RESET command. In addition, the S1 bit will be set to high during a
short-circuit (peripheral fault). It will be set back to low automatically once the
short-circuit is eliminated.
STOP