10 Error Messages
10.2 Error Messages
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
237
O-hEAt
23
The measured ambient temperature exceeds the specified value.
• Check the device's internal fan.
• Make sure that there is enough free space around the device.
If possible: Reduce load.
V-torq
25
Underload
If the motor current is 25 % below the rated motor current, this error message
appears.
OVt-Ph
49
A phase in the motor cable is not connected or is disconnected.
Sc-FO1
50
No valid field bus telegram was received within the time specified in P5-02.
• Check to make sure that the network master is working correctly.
• Check connecting cables.
• Increase the value of P5-02 to an acceptable value.
OF-01
60
No internal connection to an optional card
OF-02
61
Optional module in undefined operating state
OF-10
70
Sensor fault - overload or short circuit
Message
Error no.
[dec]
Possible cause and remedy