1 Rapid Link 5 system
1.5 Compliance with UL standards
22
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
1.5 Compliance with UL standards
1.5.1 Excerpts concerning UL conformity
The following are excerpts from the original English UL compliance docu-
ments.
1.5.1.1 RAMO (file E511778)
These devices are enclosed type AC Motor starters incorporating semiconductor switching means. These devices
are intended for installation on industrial machines in accordance with Standard for industry Machinery NFPA79.
These devices do not provide reduced voltage starting feature.
These devices do not provide isolation (isolating function).
These devices do provide motor overload protection with thermal memory and phase-loss protection.
These devices or control units have not been evaluated as providing a safety or limiting feature.
These devices are for installation in Overvoltage Category III and pollution degree 3.
Auxiliary Control outputs intended to device resilient Load.
Electrical Ratings:
Short Circuit Ratings:
Environmental Ratings: Ambient Temperature: +55 °C, Enclosure Type: 12, Markings
Short Circuit Current Ratings:
“Suitable for use on a circuit capable of delivering not more than 100 000 rms symmetrical amperes, 480 volts
maximum. Suitable for motor group installation. When protected by J class fuses rated 30A.”
“Suitable for use on a circuit capable of delivering not more than 10 000 rms symmetrical amperes, 480 volts
maximum. Suitable for motor group installation. When protected by a circuit breaker having an interrupting rating
not less than 10 000 rms symmetrical amperes, 480 volts maximum, rated 32A.”
Wiring terminals marked to indicate proper connections for the power supply, load and control circuit.
Use 60/75 deg.C copper field wiring conductors.
The ground terminals are marked with “G”, “GR”, “GRD”, “ground”, “grounding”, “PE”, or the like.
The symbol 5019. IEC publication 417, may be used, but if used alone the symbol shall be defined in the installation
Instructions provided with the equipment.
“WARNING”
"The opening of the branch circuit protective device is able to be an indication that a fault current has been
interrupted. To reduce the risk of fire or electric shock, current-caring parts and other components of the controller
should be examined and replaced if damaged.”
For Canadian installations:
“AVERTISSEMENT – L’ouverture du dispositif de protection de la dérivation peut signifier qu’un courant de défaut
a été interrompu. Pour réduire le risque d’incendie ou de choc électrique, les pièces porteuses de courant et autres
composants du contrôleur devraient être examinées et remplacées s’ils sont endommagés.”
MODEL – 400V range
INPUT
OUTPUT
BCP Fuse/
Breaker
-
(3 phase)
(3 phase)
Frame size
Model Number
FLA
FLA
Power
Power
1A
RAMO5
6.6
6.6
3 kW
3.0 HP
30A
Input Voltage 380-480/277Vac, 50/60Hz | Output Voltage 380-480VAC, 50/60Hz
MODEL
SHORT CIRCUIT RATING (kA)
Fuses (J-Type)
Breakers (Type C)
RAMO5
100kA
10kA
RAMO5-…R (with repair switch)
10kA
10kA
Содержание Rapid Link 5
Страница 1: ...Manual Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN ...
Страница 4: ...II ...
Страница 38: ...1 Rapid Link 5 system 1 10 Service and warranty 34 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 118: ...3 Installation 3 7 Isolation test 114 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 196: ...8 Parameter list 8 4 Parameter groups for RASP5 192 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 246: ...10 Error Messages 10 2 Error Messages 242 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...