6 RASP5 speed controller
6.7 Configuration of specific settings
148
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
6.7.3 Sensor inputs
The four sensor inputs SEN I1, SEN I2, SEN I3 and SEN I4 are designed for
rising-edge input signals (N/O closing contact, fail-safe).
In the factory setting, parameters P3-06, P3-07, P3-08 and P3-09 are set to 0.
When using sensors that switch to zero (normally closed), the parameters
must be set to the value 1. The signal is then inverted.
Figure 90:
Configure the sensor inputs SEN I1, SEN I2, SEN I3, SEN I4
SEN I1, SEN I2,
SEN I3, SEN I4
→
1
SEN I1, SEN I2,
SEN I3, SEN I4
→
0
Parameter
Designation
Description
Unit
Min
Max
DS
P3-06
SEN I1 logic
0: N/O closing contact
1: N/C opening contact
Note:
A change only becomes active after
POWER ON/OFF.
–
0
1
0
P3-07
SEN I2 logic
0: N/O closing contact
1: N/C opening contact
Note:
A change only becomes active after
POWER ON/OFF.
–
0
1
0
P3-08
SEN I3 logic
0: N/O closing contact
1: N/C opening contact
Note:
A change only becomes active after
POWER ON/OFF.
–
0
1
0
P3-09
SENI4 logic
0: N/O closing contact
1: N/C opening contact
Note:
A change only becomes active after
POWER ON/OFF.
–
0
1
0
→
Sensors SEN I3 and SEN I4 require a Y connector of the type
RA-XM12-Y.
Содержание Rapid Link 5
Страница 1: ...Manual Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN ...
Страница 4: ...II ...
Страница 38: ...1 Rapid Link 5 system 1 10 Service and warranty 34 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 118: ...3 Installation 3 7 Isolation test 114 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 196: ...8 Parameter list 8 4 Parameter groups for RASP5 192 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 246: ...10 Error Messages 10 2 Error Messages 242 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...