2 Engineering
2.6 Power bus
48
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
Calculate the short-circuit current and the voltage drop as specified in
DIN VDE 0100 to make sure that the protection requirements are being met.
The power bus' cable length can be calculated as follows:
Figure 18:
Example: RAMO5
Requirements for the group protection device during short-circuits.
The short-circuit current I
k
must be greater than the tripping current of the
short-circuit trip actuator I
rm
. It depends on the impedance or length of the
energy bus and the stub line.
Depending on the power bus’ length and the configuration of the power
branches, the total of all RAMO5 and RASP5 supply system currents during
continuous operation must not exceed 25 A (4-mm
2
power bus).
l =
U
0
x 1000
– Z
v
– (Z
stub
x l
stub
)
I
rm
Z
power bus
l
= Cable length (maximum: 100 m)
U
0
= 230 V (single-phase no-load voltage)
I
rm
= Tripping current of short-circuit release
z
v
= External supply impedance (e.g., 100 m
Ω
)
Z
Stub
= 35.50 m
Ω
/m (stub line 1.5 mm
2
)
Z
power bus
= 13.40 m
Ω
/m (power bus 4.0 mm
2
)
21.50 m
Ω
/m (power bus 2.5 mm
2
)
→
Take the voltage drop under load into account when selecting
the cable cross-section.
The user is responsible for taking other applicable standards
(e.g., VDE 0113, VDE 0289) into account.
3 AC 400 V∼, 50/60 Hz
I
rm
I
k
Q1
l
M
3 ∼
RAMO
1.5 mm
2
4 mm
2
I >
l
Stich
1.5 m
(4.92 ft)
1.5 m
(4.92 ft)
Содержание Rapid Link 5
Страница 1: ...Manual Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN ...
Страница 4: ...II ...
Страница 38: ...1 Rapid Link 5 system 1 10 Service and warranty 34 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 118: ...3 Installation 3 7 Isolation test 114 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 196: ...8 Parameter list 8 4 Parameter groups for RASP5 192 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 246: ...10 Error Messages 10 2 Error Messages 242 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...